Application: For measuring air temperature inside of ventilation shafts.
Available Types | RTD: Cu 50 Ω, Cu 100 Ω, Pt 100 Ω, Pt 500 Ω, Pt 1000 Ω Thermistor: 10k NTC |
Number of Elements for RTD | 1 |
Accuracy Class | RTD: 1/3B, A, B Thermistor: 1 % |
Wire Configuration |
2-, 3-, 4- Wire |
Case Type | Plastic (up to 60 °C) Aluminum (up to 100 °C) - option |
Sheath Material | 321 Stainless Steel |
Temperature Range |
-40 to 60 °C (Plastic Case) |
Response Time | 8-10 sec |
Design Features: The probe consists of ABS plastic (or aluminum) case, sealed inlet for signal cable and stainless steel tube. Open platinum or thermistor element is at the end of the tube. The probe is mounted on the surface of ventilation shaft by means of screws through the holes in the case.
Available with Mountable Transmitter (4-20 mAdc output or RS485).
If necessary to adjust the depth of immersion, a movable flange can be ordered specially for 2-10 model.
Movable flange
for 2-10 Model (option)
Probe Length, L | 40, 60, 80, 100, 120, 160, 200, 250, 320, 400, 500 mm |
Probe Diameter | 5 or 6 mm |
See articles "Types of Temperature Sensors", "Specifications of Temperature Sensors", "Calibration of Temperature Sensors", "Connection of Temperature Sensors".